This is a live sample report generated from a template — the same output you'd export as a PDF.
Sprinter van — 12V, 400W solar
NEC 690 / 706 / 710 — US off-grid, PV, energy storage
- System voltage
- 12 V
- Battery
- 2400 Wh
- Solar
- 400 W
- Peak load
- 120 W
- Wire runs
- 5
Bill of materials
1× Solar panel Renogy400 W
1× Charge controller Victron50 A
1× Battery Battle Born200 Ah @ 12 V
1× Fuse Blue Sea250 A
1× Inverter / charger Victron2000 W continuous
1× DC load —120 W
Compliance
✓ NEC 690.8(A)(1) Charge controller rated ≥125% of PV short-circuit current.
✕ NEC 240.4 Fuse 250A exceeds the 200A ampacity of its 3/0 AWG conductor — protect the wire, not just the load.
✕ NEC 240.4 Fuse 250A exceeds the 200A ampacity of its 3/0 AWG conductor — protect the wire, not just the load.
! Design Inverter has no battery or busbar feeding it.
ℹ Best practice No battery monitor/shunt — recommended for accurate state-of-charge.
Design documentation only — not a P.Eng-stamped drawing. Verify with a licensed professional before installation.