Sprinter van — 12V, 400W solar
NEC 690 / 706 / 710 — US off-grid, PV, energy storage · Rev A · 2026-07-21
The actual output of the CircuitProof engine — deterministic wire sizing, breaker selection, and code checks run against NEC 690 / 706 / 710 — US off-grid, PV, energy storage. The same report exports as a 9-page permit-ready PDF.
Rev A · NEC 690 / 706 / 710 — US off-grid, PV, energy storage
12 V
System voltage
2,400 Wh
Battery bank
400 W
Solar array
120 W
Peak load
5
Wire runs sized
3
Items to review
| Qty | Item | Mfr | Spec |
|---|---|---|---|
| 1× | Solar panel | Renogy | 400 W |
| 1× | Charge controller | Victron | 50 A |
| 1× | Battery | Battle Born | 200 Ah @ 12 V |
| 1× | Fuse | Blue Sea | 250 A |
| 1× | Inverter / charger | Victron | 2000 W continuous |
| 1× | DC load | — | 120 W |
| From | To | AWG | Breaker | VD |
|---|---|---|---|---|
| Solar panel | Charge controller | 12 | 15 A | 2.8% |
| Charge controller | Battery | 6 | 70 A | 1.2% |
| Battery | Fuse | 4/0 | 225 A | 0.2% |
| Fuse | Inverter / charger | 4/0 | 225 A | 0.2% |
| Battery | DC load | 12 | 20 A | 2.9% |
compliance
Code checks against NEC 690 / 706 / 710 — US off-grid, PV, energy storage.
Charge controller rated ≥125% of PV short-circuit current.
Fuse 250A exceeds the 200A ampacity of its 3/0 AWG conductor — protect the wire, not just the load.
Fuse 250A exceeds the 200A ampacity of its 3/0 AWG conductor — protect the wire, not just the load.
Inverter has no battery or busbar feeding it.
No battery monitor/shunt — recommended for accurate state-of-charge.