Code reference · NEC 220.12; 220.52; Table 220.45; Table 220.55 Col C; 220.54

NEC 220 standard-method dwelling load calc, worked

Standard method, 2,000 ft² dwelling: general lighting 2,000 × 3 VA = 6,000 VA; two small-appliance circuits 3,000 VA; laundry 1,500 VA → 10,500 VA gross.

Apply Table 220.45 demand: first 3,000 VA at 100% + remaining 7,500 at 35% = 5,625 VA. Add a 12 kW range at its Column C demand (8,000 VA) and a 5.5 kVA dryer (5,500 VA, above the 5,000 floor).

Total 19,125 VA ÷ 240 V ≈ 80 A calculated load — why a 100 A service is the floor for a modest all-gas-cooking-excepted dwelling, and 200 A is standard once EV charging or electrification enters.

Run the numbers yourself

Need this as a permit-ready document?

One Document Credit ($29) buys a full clause-cited compliance PDF — wire sizing, voltage drop, overcurrent protection, every value traceable to the section it came from.

Get your document →

Every numeric value on this page is computed by the CircuitProof calculation engine — the same golden-tested code that renders our permit documents — not typed by hand. Code text is paraphrased and cited; always verify against your jurisdiction's adopted edition and a licensed professional before installation. Design documentation, not a stamped drawing.